ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

68



Training Status
Training Status is present on this page because one or more fields or graphs shows data
that was gathered during the training process. The field shows one of the following states:

Training Enabled - which indicates system data is being recorded. Training should

run during normal system behavior.

Training Disabled - which indicates NO system data is being recorded.

Training Complete which indicates that the time period for training has expired and

the data is stored in the positioner.



Action Buttons
The Apply button will save changes to the connected device.


The Retrieve button will retrieve the latest information from the device.


Warning and Alarms

Friction High

Definition: The valve and actuator friction has passed the user set

limit.

Implications: High friction can cause loop oscillations, poor position

control, jerky motion, or valve sticking. It can be caused by build-up
from the process on the stem, trim or seat , by a failing bearing or
guides in the valve and actuator, galling of the trim or stem, excessively
tightened packing, linkages, or other valve or actuator mechanical
issues.

Possible Solutions: Determine if the friction is significantly interfering

with the valve control. If not, consider increasing the friction warning
limit. Consider the following to reduce friction: Stroke the valve to clear
off build-up. Clear any external mechanical obstruction, loosen the
packing, clean the stem, repair or replace the actuator. Highly localized
friction or very jerky travel can indicate internal galling. Repair or
replace internal valve components.

Friction Low

Definition: The friction has passed below the user set limit.

Implications: Low friction is an indication of improperly loaded packing

and, in severe cases, can be an indication of the process fluid leaking at
the valve stem.

Possible Solutions: Check for packing leak. Tighten or replace the

valve packing.