ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

49


Position Range Small

Definition: During calibration, the range of motion of the position

feedback arm was too small for optimum performance.

Possible Solutions: Check for loose linkages and/or adjust the

feedback pin to a position closer to the follower arm pivot to create a
larger angle of rotation and recalibrate. The minimum angle of rotation
should be greater than 15 degrees. Briefly pressing the QUICK-
CAL/ACCEPT button acknowledges this condition and the positioner
will operate using the short stroke calibration if otherwise a good
calibration.

Position < ADC Range

Definition: During calibration, the feedback sensor moved beyond its

range of operation at the 0% (closed) position.

Possible Solutions: Adjust the positioner mounting, linkage or

feedback potentiometer to move the position sensor back into range
then restart the calibration.

Position > ADC Range

Definition: During calibration, the feedback sensor moved beyond its

range of operation at the 100% (open) position.

Possible Solutions: To correct the condition, adjust the positioner

mounting, linkage or feedback potentiometer to move the position
sensor back into range then restart the calibration.

No Motion Time Out

Definition: During a stroke calibration, there was no valve motion

detected. Because some valves are quite large, this indicator can take
up to 9 minutes to detect an error.