Flowserve Logix MD+ ValveSight User Manual

Page 208

Advertising
background image

ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

208


Yellow

circle indicates that an active warning, alert or mode is

present.

Red

circle indicates that an active alarm or state is present that

could seriously limit the operation of the valve.

Gray

circle indicates that the feature or condition is not available

because the configuration of the hardware or software does not support
it.

A checkbox indicates the masked status. Check to mask. If a particular

indicator is masked, it will not be shown in the active indicator field at the top
of each screen, affect the status of the health bars on the main dashboard, be
sent in command 48, or be seen on the blinking LEDs on the positioner. It
will however continue to show on this page.

Clicking on a button will display the Implications and Possible Solutions for

that flag.


Action Buttons
The Apply button will save changes to the connected device.


The Retrieve button will retrieve the latest information from the device.


Stroke Calibration Flags

Stroke Calibration Required

Definition: A factory reset was performed and the positioner has not