■ Where contact outputs are desired to be provided when a measurement value comes to a target value

(SV start)
Setting example for output 1 to be provided for 1 minute after 180 °C is reached

SEt04

CNt

Name

Setting content

Setting value

SV

Control setting

180

C

180

SEt5
oUt1

Name

Setting content

Setting value

o1F

Target connection setting

Timer 1 output

5

SEt04

tIME1

Name

Setting content

Setting value

tMF1

Function setting

SV start

3

tSV1

Start SV permissible range setting

Give range of 2 °C

2

oFt1

Off delay timer

1 minute

00:01



Temperature

180℃

Normal

temperature

Output 1

ON

OFF

Contact output is provided for 1 minute

Setting the start SV permissible range
setting to 2 °C results in timer
operation when the value falls in the
range of SV ± 1 ℃.