6.2 Remote SV input type setting

■ Remote SV input type setting

SEt02

INP2

Setting content

Initial value

1

INP2

Press the MODE key for making a setting effective (including reverse feed).

18

16 to 20

See the remote SV input type setting table.

Set the input type of the remote SV input.
The remote SV input is a multiinput of voltage and current. Set the remote SV input according to the input being used.

■ Remote SV input type setting table

Setting

No.

Input type

Connection

Measurement/

setting range

Indicator resolution

Accuracy

16

0 - 1 VDC

I/V

-19999 to +29999
Display resolution to be
20000 or less

Random change of
decimal point
position allowed

± 0.3 % ± 1 digit of full scale

17

0 - 5 VDC

I/V

18

1 - 5 VDC

I/V

19

0 - 10 VDC

I/V

20

4 - 20 mADC

I/V


*1 The display range of analog input is min. - 19999 digits and max. +29999 digits. The range, however, can be narrowed by

setting the scaling upper limit (FSH 2) and lower limit (FSL 2) settings. See below for the narrowed display range.

<Where input is 0 - 1 V/0 - 5 V/0 - 10V>

• Display of the lower limit side: Up to - 2 % of the full scale
• Display of the upper limit side: Up to + 12 % of the full scale

<Where input is 1 - 5 V/4 - 20 mA>

• Display of the lower limit side: Up to - 12 % of the full scale
• Display of the upper limit side: Up to + 12 % of the full scale


Full scale is defined as the range from FSL 2 to FSH 2.

Remote SV input connection table

Model

TTM-200 Series

Model No.

204

205
209

207

Connection

Wiring

Terminal No.

Terminal No.

Terminal No.

I/V

17
18

11
12

■ Display scaling upper limit/lower limit setting

SEt02

INP2

Setting content

Initial value

2

FSH2

FSL 2 to SV setting range upper limit
The unit depends on the input type setting for the input 1.

1200

3

FSL2

SV setting range lower limit to FSH 2
The unit depends on the input type setting for the input 1.

0

Set the display scaling upper limit/lower limit for the remote SV input.
The input type of the remote SV input can be set only for voltage or current input.