■ Forward/reverse operation setting

SEt04

CNt

Setting content

Initial value

10

dIR

0

Reverse operation

0

1

Forward operation


Set the forward/reverse operation of the primary control.

<Reverse operation>
• Reverse operation (heating control) is a control where the operating amount increases as PV (measurement value) lower

than SV (setting value).

MV

100

Low

SV

High

<Forward operation>
• Forward operation (cooling control) is a control where the operating amount increases as PV higher than SV.

MV

100

Low

SV

High

Note Take care the following when setting the secondary control.

• The secondary control is automatically set to the forward operation when the primary control is set to 0 or the reverse

operation.

• The secondary control is automatically set to the reverse operation when the primary control is set to 1 or the forward

operation.