TOHO ELECTRONICS TTM200 User Manual

Page 202

Advertising
background image

48-7009-E

6-54

■ Event function 4 (loop abnormality)

SEt05

oUt1

to

SEt11

oUt7

Setting content

Initial value

9

E1F4

to

E7F4

Function

00

*0

Nonexistent

*1

Existent

Add-on function

0*

None

1*

Hold


Set the event function 4 (loop abnormality).
Event function 4 is a function that detects output abnormalities, and that outputs signals from the event output.
This function can be used when the event function 4 is set and the target connections of the outputs 1 to 7 are set to event
outputs.


For details of the setting of the loop abnormality, see section “5.4.6 Loop abnormality function” on pages 5-38 and 39.

For the setting of the loop abnormality time, see section of primary/secondary control loop abnormality time setting on pages
6-27and 40






■ Event polarity setting

SEt05

oUt1

to

SEt11

oUt7

Setting content

Initial value

10

E1P to E7P

0

Normal open

0

1

Normal close

Set “close active” or “open active” for the event function setting.

Close active: Event function closes when the event output is in the active state.
Open active: Event function opens when the event output is in the active state.