TOHO ELECTRONICS TTM200 User Manual

Page 187

Advertising
background image

48-7009-E

6-39

■ Secondary control loop anomaly PV threshold

SEt04

CNt

Setting content

Initial value

47

tS2

Thermocouple/resistance temperature detector input
0.0 to 999.9 (°C)0 to 999 (°C)

0

Voltage/current input

0 to 9999 (digit)



Set the secondary control loop anomaly PV threshold .

The function is to detect an abnormality in the control loop.
When width of tS1 has PV from an SV , a judgment of the loop anomaly acts.
The real judgment in PS2 and LoP2.

For details, see section “Loop abnormality function” on pages 5-38 and 39.



Control loop

anomaly PV

threshold

(TS2)

SV

setting

value

(TS2)

PV

When PV is out of the judgment

domain, the control loop anomaly is

not judged.

PV indicates present temperature.

Temperature threshold is a value

specified by [SV

– TS2].

Judgment

domain

Non-

judgment

domain

Advertising