5.1 Precautions on operating the equipment

Before beginning operation or turning on the power, check the following.

★ Operation for turning on the power

The equipment is not equipped with a power switch. Connecting a power will turn the power of the
unit ON. The initial screen is displayed for about 4 seconds, and then the equipment operates.

The control mode for the control setting mode is set for RUN (control start) in factory default. After
wiring is complete and the setting value (SV) is set, the control starts.

At factory default, the control method is set for the PID control.

* Proportional band: 3.0 %
Integration:

0 second

Derivation:

0 second

Proportional cycle: Relay contact output

20 seconds

SSR drive output

1 second


★ Behavior during input abnormality

Open or short (only for a resistance temperature detector) of input signals is determined as an input
abnormality (such as burnout) by the equipment.

Input type

Display on the

equipment

Operation of control

output

Operation of event

output

Thermocouple


Overscale

Operating amount

limiter lower limit

Analogous to the

setting for at-input

abnormality.

(See pages 6-39 to

41.)

Resistance temperature detector

0 - 10 mVDC

0 - 1 VDC



Underscale

0 - 5 VDC

1 - 5 VDC

0 - 10 VDC

4 - 20 mADC

* Burnout function: A function to forcibly move outputs of a controller toward upper limit or lower

limit (safety side) in case the wires are disconnected on a thermocouple or resistance temperature
detector.


★ Checking each parameter

Set each parameter such as setting value (SV) or PID to a value that is appropriate for the subject of
control.
For details of setting each parameter, see the item 6 “Parameter setting.”
For details of switchover setting of RUN (control start) and READY (control stop), see pages 5-20 and
21.


★ Operation at power-outage (momentary outage)

There is no effect on operation in case of outage in 1 cycle or less.

1 cycle

50 Hz

20 ms

60 Hz

16.7 ms


For DC power with the outage for 40 ms or shorter, there is no effect on operation.
In case of the outage for longer than 40 ms, the equipment is reset.