48-7009-E

6-9

PV

Remote SV input

4mA

20mA

100.0%(FSH2)

0.0%(FSL2)

Note

(1) Display resolution is 20,000 or less.

Take care it when the range from FSL 2 to FSH 2 is set larger than 20,000.
Setting example:

Fluctuation or missing value of PV may be caused when the remote SV input is set to the input type
of 4 - 20 mA, FSL 2 to -19999 digits and FSH 21 to 29999 digits.

(2) Take care that setting values for FSH 2 and FSL 2 can be the same.

■ PV compensation gain/PV compensation zero setting

SEt02

INP2

Setting content

Initial value

4

PVG2

0.500 to 2.000 (times)

1.000

5

PVS2

Thermocouple/resistance temperature detector
-999.9 to 999.9 (

C)

-999 to 999 (

C)

0

Voltage/current input
-9999 to 9999 (digit)

PV compensation gain setting: PV (measurement value) for the remote SV input is multiplied by the compensation value.
Setting example: Where PV of the equipment is displayed for 90°C and the actual temperature is 100°C, and the display is

to be compensated to 100°C, using the PV compensation gain setting.

The display after PV compensation is about 100°C = 90°C (before PV compensation) × 1.111.

PV

PVG 2 = 100/90 = 1.111 times

100

90

After PV compensation
Before PV compensation

100 Actual temperature