■ PV filter setting

SEt01

INP1

Setting content

Initial value

11

PdF1

0.0 to 99.9 (seconds)

0.0

The PV filter setting is a function that demonstrates the CR filter effect on software through performing a first-order lag calculation for
PV of the input 1.

The filter effect is set using the time constant [t].

(Time constant is defined as the time required for PV to reach about 63 % when an input changes in a step configuration.)

* CR filter --- a filter of first-order lag

Note Application of PV filter

(1) Effect of noise is alleviated due to elimination of high-frequency noise when electric noise applies on inputs.
(2) Response can be delayed against abrupt change of an input.

100%

0%

Time

100%

0%

Time

100%

0%

Time

63%

Time constant (t)

■ Input signal




■ Input read in

When no digital PV filter exists

[Time constant (t) = 0]


When a digital PV filter exists

[Time constant (t) > 0]

■ Decimal point position setting

SEt01

INP1

Setting content

Initial value

12

dP1

Thermocouple/resistance temperature detector input

0

0

Unit of 1°C

0.0

Unit of 0.1

C

Current/voltage input

0

1/digit

0.0

0.1/digit

0.00

0.01/digit

0.000

0.001/digit

0.0000

0.0001/digit

A decimal point position is set for PV of the input 1.

■ °C/°F switchover

SEt01

INP1

Setting content

Initial value

13

C/F1

Press the MODE key for making a setting effective (including
reverse feed).

°C

°C

Celsius

°F

Fahrenheit

Set the unit of temperature input.

Note Switchover of °C/°F may result in change of each setting value due to limits being applied, such as SLH, SLL, tRH and

tRL.