48-7009-E

5-54

*5: Bank setting (St*bK)

Switchover is made for each step of a program. “Bank No.” can be designated.

Setting range: St*bK = 0 to 7 (The range depends on SET 4 bANKH.)

Initial value: St* bK = 0 (* = 1 to 8)

Note The symbol “*” of the parameter setting display “St*bK” indicates “step No.”

(The range depends on SET 22 StEPN.)

Note Effective only during a program run

Note When the bank automatic switching function is used (SET 23 BAF

1), no display

appears. The bank automatic switching function is prioritized over the “bank No.”
designation.



*6: Step time (tIM*)

Sets the step time of a program.

Setting range: tIM* = 00:00 to 99:59

Initial value: 00:00 to (* = 1 to 8)

Note The symbol “*” of the parameter setting display “tIM*” indicates “step No.”

(The range depends on SET 22 StEPN.)

Note The time unit is set in the time unit setting (SET 21 H/MP).

Note With the setting value of “00:00,” a run unlimitedly continues.