48-7009-E

6-25

■ Primary control abnormality operating amount setting

SEt04

CNt

Setting content

Initial value

28

FAL1

Digital output
0.0 to 100.0 (%)

0.0

Analog output
-10.0 to 110.0 (%)

Set the primary control at-abnormality operating amount setting.
This operating amount is the one provided in case of failure of gauges and such.
<Conditions on the primary control at-abnormality operating amount>

• Burn-out
• Err 1 (AD abnormality error)
• Err 2 (AT error)

Note

(1) The operating amount is output without constraint from MLH 1 (primary control operating amount limiter upper limit) or

MLL 1 (primary control operating amount limiter lower limit).

(2) Burn-out during the manual control results in outputting the operating amount that is set in MV 1 (primary control

operating amount).

(3) The operating amount cannot be set during the control type of ON/OFF control. (No screen is displayed.)