48-7009-E

6-82

Zone Threshold* Setting

SEt23

ZbNK

Setting Contents

Initial

Value

3

PM*

Zone Threshold* Setting 3

1200

Setting Range

SV Limiter Lower Limit (SLL) to SV Limiter
Upper Limit (SLH) <PM* <= PM*+1>

(PM*) will depend on the setting value of
bANKH

PM7 PM6~SLH
PM6 PM5~SLH
PM5 PM4~SLH
PM4 PM3~SLH
PM3 PM2~SLH
PM2 PM1~SLH
PM1 SLL~SLH

Setting of the Threshold is done for the Bank
Automatic Switching which will be done for *
= 1 to 7 (8 bank row).

When SET04 bANKH=0, the setting will be invalid.
There will be no indication either.

※ 3

Setting of the Threshold is done for the Bank Automatic Switching which will be done for the Zone

Threshold*Setting (PM1 to PM7) <Max. 8 banks>

Setting Range: SLL to SLH
Threshold can be set to max. of 7 (8 banks).
The initial value set is 1200 for PM1 to PM7. The bank switching by selected source will not be done.

NOTE: The setting range is PM*SV Limiter Lower Limit (SLL) to SV Limiter Upper Limit, but when the

value of the PM(*・1) is set exceeding the PM(*), the PM (*) will be changed together.

The selectable range of the Zone Threshold*Setting (PM*) will depend on the setting value of bANKH.

SET04

bANKH=

Selectable PM*

0 PM No Indication
1 * = 1
2 * = 1~2
3 * = 1~3
4 * = 1~4
5 * = 1~5
6 * = 1~6
7 * = 1~7

Note: the parameters indicated will vary depending on the value of SET04 BANKH.