TOHO ELECTRONICS TTM200 User Manual

Page 111

Advertising
background image

48-7009-E

5-41

■ Calculation of the CT 1 abnormal current value setting

Detection current to be set is calculated with the following equation as an indication:

∴ CT 1 abnormal current value setting value = Current normal value + current at heater disconnection

2

Note Take care that the current in a multiplication factor of N flows when the load wire is wound

around CT N times due to too small a measurement current. Sixty amperes or 6 times the
actual current of 10 A flows when the load wire is wound around CT 6 times.

Example: Heater of 100 V, 2kW
[When normal]


[When disconnected]

Load

Load

To equipment
CT input

To equipment
CT input

Disconnected



The current on the heater is 20 A at normal and 0 A at disconnected, thus the CT 1 abnormal current value
setting value is as follows.

∴ CT 1 abnormal current value setting value =

Current normal value + current at

heater disconnection

2

20 + 0

2

=

= 10 [A]


■ Example of parameter setting

The example shown below is identical to the above example, except where CT 1 is installed on the
output 1 and CT abnormality is provided as output on the output 2.

SEt6
oUt2

Name

Setting content

Setting value

o2F

Target connection setting

Event output

2

E2F3

Event function 3 setting (CT
abnormality)

All modes, no added function, CT 1
abnormality

001

SEt12

CT

Name

Setting content

Setting value

CI1

CT 1 target connection setting

Connected to OUT 1 (allowed to be
set in case of DO)

1

Ct1

CT 1 abnormal current value setting

10.0