TOHO ELECTRONICS TTM200 User Manual

Page 114

Advertising
background image

48-7009-E

5-44

■ V connection

Example: Where 2 heaters of 200 V and 2 kW are used

[When normal]

To equipment
CT input

To equipment

CT input

Load

Load

The current that flows in the target device for CT installation is 17.3 A (≒√3 × 10 A).

[Disconnected on the common side]

To equipment
CT input

To equipment

CT input

Load

Load

[When disconnected on load side]

To equipment
CT input

To equipment

CT input

Load

Load

Disconnected

Disconnected

Current when disconnected = 10A

(1/2)

= 5A

Current when disconnected = 10A

1

= 10A

The heater disconnection detection current value when disconnection occurs on the common side is as
follows.

Heater disconnection detection current value = (17.3 +5)/2 ≒ 11.2 [A]

The heater disconnection detection current value when disconnection occurs on the load side is as
follows.

Heater disconnection detection current value = (17.3 +10)/2 ≒ 13.7 [A]

Hence, the heater disconnection detection current value is to be 13.7 A in order to detect disconnection
in both cases.


■ Example of parameter setting

The following is an example when CT 1 and 2 are installed on the outputs 1 and 2 respectively in the
connection shown above and CT abnormality is provided as output on the output 3.

SEt6
oUt2

Name

Setting content

Setting value

o3F

Target connection setting

Event output

2

E3F3

Event function 3 setting (CT
abnormality)

All modes, no added function, CT 1
abnormality + CT 2 abnormality

003

SEt12

CT

Name

Setting content

Setting value

CI1

CT 1 target connection setting

Connected to OUT 1 (allowed to be
set in case of DO)

1

Ct1

CT 1 abnormal current value setting

13.7

CI2

CT 2 target connection setting

Connected to OUT 2 (allowed to be
set in case of DO)

2

Ct2

CT 2 abnormal current value setting

13.7