TOHO ELECTRONICS TTM200 User Manual

Page 112

Advertising
background image

48-7009-E

5-42

■ For 3-phase

■ Delta connection

Example: Where 3 heaters of 200 V and 2 kW are used


[When normal]

To equipment
CT input

To equipment
CT input

Load

Load

Load

Normal current is 17.3 A (≒√3 × 10 A) for each phase.


[When disconnected in between phases]

To equipment
CT input

To equipment
CT input

Load

Load

Load

To equipment
CT input

To equipment
CT input

Load

Load

Load

[When disconnected on load side]

Disconnected

Current when disconnected = 10A

√3

(√3/2)

= 15A

Disconnected

Current when disconnected = 10A

√3

(1/√3)

= 10A

The heater disconnection detection current value when disconnection occurs in between phases is as
follows.

CT 1 abnormal current value setting value = (17.3 + 15)/2 ≒ 16.1 [A]


The heater disconnection detection current value when disconnection occurs on the load side is as follows.

CT 1 abnormal current value setting value = (17.3 + 10)/2 ≒ 13.65 [A]


For detection in both cases, the CT 1 abnormal current value setting value is to be 16.1 A.