TOHO ELECTRONICS TTM200 User Manual

Page 201

Advertising
background image

48-7009-E

6-53

■ Event function 3 setting (CT abnormality)

SEt05

oUt1

to

SEt11

oUt7

Setting content

Initial value

8

E1F3

to

E7F3

Function

000

**0

None

**1

CT 1 abnormality

**2

CT 2 abnormality

**3

CT 1 abnormality + CT 2 abnormality

Add-on function

*0*

None

*1*

Hold

*2*

Delay

*3*

Hold + delay

Control mode interlocking function

0**

All modes

1**

RUN/MAN mode only

2**

RUN mode only


Set the event function 3 (CT abnormality).
Event function 3 is a function to detect the current flowing in the heater that is assigned in the outputs 1 to 7 as target
connections, using the current transformer (CT) that is supplied as an accessory, and to compare the detected current to the CT
abnormality current.
This function is useful for detecting disconnected wiring to the heater or adhesion of a relay contact that turns on and off the
electricity to the heater.

For the details regarding the connection and setting of CT (current transformer), please refer
to Operation Manual CT (P5-40 to 44).