TOHO ELECTRONICS TTM200 User Manual

Page 250

Advertising
background image

48-7009-E

7-19

7.5.5 Control setting mode (SET 04) (4/4)

Setting data

Character

Setting (monitor) value

Initial value

Unit

Setting

value

Blind

Secondary control
at-abnormality
operating amount

FAL2

Digital output: 0.0 to 100.0
Analog output: -10.0 to 110.0

0.0

%

Secondary control
loop anomaly PV
threshold

tS2

Temperature: 0.0 to 999.9

0 to 999

Analog: 0 to 9999

0

C

Digit

Secondary control
loop anomaly MV
threshold

MS2

MLL2 to MLH2

100.0

%

Secondary control
loop anomaly PV
change threshold

PS2

Temperature: 0.0 to 999.9

0 to 999

Analog: 0 to 9999

0

C

Digit

Secondary control
loop abnormality time

LoP2

0 to 9999

0

Second

Secondary control
sensitivity

C2

Temperature: 0.0 to 999.9

0 to 999

Analog: 0 to 9999

0

C

Digit

Secondary control
off-point position

CP2

Temperature: -999.9 to 999.9

-999 to 999

Analog: -9999 to 9999

0

C

Digit

Secondary control off
protection timer

Fdt2

0 to 99

0

Minute

Secondary control
protection on timer

Ndt2

0 to 99

0

Minute

Manual reset

Pbb

0.1 to 100.0

0.0

%

Dead band

db

Temperature: -999.9 to 999.9

-999 to 999

Analog: -9999 to 9999

0

C

Digit

Ramp time

RMP

Temperature: 0.0 to 999.9
Analog: 0 to 9999

0.0

C/minute

Digit

/minute

Valve motor stroke
time

VLt

0.1 to 999.9

3.0

Second

Valve motor drive
dead band

Vdb

0.0 to 100.0

1.0

%

Post-AT initial
opening ratio

ASP

0.0 to 100.0

50.0

%

Note

(Ndt2) is selectable only on Ver3.xx or later.

Note The (RMP) function will turn OFF at setting value "0" or "0.0".