48-7009-E

5-23

Re-execution of AT
PID parameters calculated by AT are not necessarily best suited for all states.
Re-execute AT because best suited control may not be possible for cases listed below where settings or
states are changed.

Changes on other than this
equipment

Changes on this equipment

Sensor (changed to different
type)

Setting of input type

Control type setting

Forward/reverse operation
setting

Output (heater or power
supply)

Great change of SV

PID control type

Tuning type setting

Change of operation of
controlled subject

SV limiter upper limit and
lower limit

Type B mode

Primary/secondary control
operating amount limiter

Primary/secondary control
proportional band setting

Integral time setting

Derivative time setting

Anti-reset windup

Valve motor stroke time



■ Special operation of AT

① AT starts also when READY is set for DI, using the AT start screen or AT start/stop based on the

key function setting.

② AT continues when the control is changed from RUN to READY or vice versa, or changed from

Manual to Auto or vice versa for DI during AT.

③ The operation switches over from reverse to forward or vice versa for DI even during AT.


■ How to start/stop AT

AT can start in any state, such as control stop, temperature in rise or control in stability, as long as the
control is effective after power-on.
① Move to the setting item selection screen by prolonged pressing of the MODE key in the run

mode (power-on initial screen).

② Have the control setting mode (SET 04) displayed by pressing the ▽/△ key in the setting item

selection screen.

③ Have the AT start screen displayed by pressing the MODE key several times.
④ AT is executed by pressing the ▽/△ key. SV and AT alternately blinks on and off in the SV

screen during AT. Press the ▽/△ key to stop AT. The screen returns to the AT start screen.

⑤ The screen returns to the AT start screen when AT is complete. Upon the completion, PID

parameters are automatically set.

⑥ Prolonged pressing of the MODE key returns the mode to the operating mode.