48-7009-E

5-68

■ Regarding switchover of the input types

If input 1 type [INP 1] is set in a bank, an operation of switching the input type can be executed during
a program run by using the “step* designated bank setting [St*bK] ” function.

Note Note that the input type must be selected from the same group as listed below. Input types from

different groups should not be mixed. Otherwise, switching the decimal point malfunctions.

Input 1 type in Group A

Setting

No.

Input type

Connection

Measurement/

setting range

Designation

resolution

Group A

0

K thermocouple

TC

-200.0 to +1372.0

1

C/0.1

C

Input type: thermocouple
Decimal point: 0 or 0.0

1

J thermocouple

TC

-200.0 to +1200.0

1

C/0.1

C

2

T thermocouple

TC

-200.0 to +400.0

1

C/0.1

C

3

E thermocouple

TC

-200.0 to +1000.0

1

C/0.1

C

7

N thermocouple

TC

-200.0 to +1300.0

1

C/0.1

C

8

U thermocouple

TC

-200.0 to +400.0

1

C/0.1

C

9

L thermocouple

TC

-200.0 to +900.0

1

C/0.1

C

12

PL II thermocouple

TC

0.0 to +1390.0

1

C/0.1

C


Input 1 type in Group B

Setting

No.

Input type

Connection

Measurement/

setting range

Designation

resolution

Group B

4

R thermocouple

TC

-50 to +1768

1

C

Input type: Thermocouple
Decimal point: 0

5

S thermocouple

TC

-50 to +1768

1

C

6

B thermocouple

TC

0 to +1800

1

C

10

WRe5-26 thermocouple

TC

0 to +2300

1

C

11

PR40-20 thermocouple

TC

0 to +1880

1

C


Input 1 type in Group C

Setting

No.

Input type

Connection

Measurement/

setting range

Designation

resolution

Group C

13

Pt100

RTD

-200.0 to +850.0

1

C/0.1

C

Input type: Resistance
temperature detector
Decimal point: 0 or 0.0

14

JPt100

RTD

-200.0 to +510.0

1

C/0.1

C


Input 1 type in Group D

Setting

No.

Input type

Connection

Measurement/

setting range

Designation

resolution

Group D

15

0 - 10 mVDC

TC

-19999 to +29999
Display resolution to
be 2000 or less

Random
change of
decimal point
position
allowed

Input type: Resistance
temperature detector
Decimal point: 0 or 0.0
0.00 or 0.000
or 0.0000

16

0 - 1 VDC

I/V

17

0 - 5 VDC

I/V

18

1 - 5 VDC

I/V

19

0 - 10 VDC

I/V

20

4 - 20 mADC

I/V

* The decimal point setting for each bank can vary in a same group.