4 control function setting, Control function setting -14 – TOHO ELECTRONICS TTM200 User Manual

Page 162

Advertising
background image

48-7009-E

6-14

6.4 Control function setting

■ Bank switchover/Bank Upper Limit Setting

SEt04

CNt

Setting content

Initial value

1

bANK

0 to 7

Bank 0 to 7

0

bANKH

Bank Upper Limit Setting 0 to 7

3

7

Switching over to the banks 0 to 7 is executed.

Switchover to either one of the banks 0 to 7 results in that a parameter set in the memory bank is switched over to a setting
value for each bank.

Note The setting is determined by pressing the MODE key or FUNC key (only for setting the screen reverse feed).

For the Bank Function, please refer to Operation Manual Bank Function (P5 – 28 up to 30).


■ Control setting

SEt04

CNt

Setting content

Initial value

3

SV

SLL to SLH

0

Set a target value (SV) for a control.

Allowable setting range is from SLL (SV limiter lower limit) to SLH (SV limiter upper limit).


■ SV limiter upper limit/lower limit

SEt04

CNt

Setting content

Initial value

4

SLH

Thermocouple/resistance temperature detector input
(SLL + 5.0) to SV setting range upper limit (°C)
(SLL + 5) to SV setting range upper limit (°C)

1200

Voltage/current input
(SLL + 50) to SV setting range upper limit (digit)

12000

5

SLL

Thermocouple/resistance temperature detector input
SV setting range lower limit to (SLH - 5.0) (°C)
SV setting range lower limit to (SLH - 5) (°C)

0

Voltage/current input
SV setting range lower limit to (SLH - 50) (digit)

Set the SV upper limit/lower limit.
• SV limiter upper setting range

For input of thermocouple/resistance temperature detector

: (SLL + 5) to Input 1 setting range upper limit [°C] (Decimal point position setting 0)
: (SLL + 5.0) to Input 1 setting range upper limit [°C] (Decimal point position setting 0.0)

For input of voltage/current

: (SLL + 50) to Input 1 setting range upper limit [digit]

• SV limiter lower setting range

For input of thermocouple/resistance temperature detector

: Input 1 setting range lower limit to (SLL - 5) [°C] (Decimal point position setting 0)
: Input 1 setting range lower limit to (SLL - 5.0) [°C] (Decimal point position setting 0.0)

For input of voltage/current

: Input 1 setting range lower limit to (SLL - 50) [digit]


For input 1 setting range upper limit/lower limit, see the input 1 type setting table on page 6-2.

Advertising