3 wiring to each terminal, Wiring to each terminal -7 – TOHO ELECTRONICS TTM200 User Manual

Page 29

Advertising
background image

48-7009-E

3-7

3.3 Wiring to each terminal

In connection diagrams, left side of the terminal number represents inside the equipment while right side
shows the external side of the equipment.

★ Power supply

TTM-204

Terminal Nos. ① and ②

TTM-205

TTM-207

TTM-209

TTM-204

Type of power supply

Fluctuation range

Frequency

Power consumption

100 to 240 VAC

85 to 264 VAC

50/60 Hz

10 VA or less

24 VAC

21.6 to 26.4 VAC

50/60 Hz

4 W or less

24 VDC

21.6 to 26.4 VDC

4 W or less

TTM-205/207/209

Type of power supply

Fluctuation range

Frequency

Power consumption

100 to 240 VAC

85 to 264 VAC

50/60 Hz

11 VA or less

24 VAC

21.6 to 26.4 VAC

50/60 Hz

6 W or less

24 VDC

21.6 to 26.4 VDC

6 W or less

* Wire the power supply for instruments in such a way that they don’t receive noise from the power supply of the

power devices.

The use of a noise filter is recommended in case that the equipment is vulnerable to noises.

Take care the following when a noise filter is used.

Install the noise filter as close to a temperature controller as possible.

Wire the instruments in as short a distance as possible to output lines (secondary side) of the noise filter and
power terminals for the temperature controller.

Isolate the noise filter input line (primary side) from its output line (secondary side).

High-frequency elements of noises may be induced, resulting in no provision of much noise attenuation effect as
expected, in case of input and output wires being close one another, such as being bundled together or installed in
a same duct or tube.

Wire the grounding wire of the noise filter in as short a distance as possible.

A long grounding wire is equivalent to insert of an inductance, resulting in deteriorated high-frequency
characteristics.

Before installing the noise filter, peel off the paint applied on a mounting plate of the noise filter as appropriate, in
order to reduce the contact resistance between the noise filter and equipment housing.

* For the power supply, use and twist wires that has lesser voltage drop.

* It takes about 4 seconds for the unit to activate after its power is turned on. Use delay relays when

using the equipment for generating signals for interlocking circuits.

* In case of using the equipment with a 24 V power supply, supply the power from a SELV circuit

(power supply secured with safety).

* The equipment is not supplied with power supply switch fuses. Separately install fuses in proximity

of the equipment, as needed.
◎ Recommended fuse rating: Rated voltage of 250 V and rated current of 1A

* The input power supply and the input/output are isolated one anther on the equipment.

* Isolation diagram
Where relays and open collectors are included in
outputs


Where outputs are SSRs, current outputs or voltage
outputs

Power supply circuit

Power supply circuit

PV input

CPU circuit

Output 1

PV input

CPU circuit

Output 1

AI input

Output 2

AI input

Output 2

CT input

Outputs 3 to 7

CT input

Outputs 3 to 7

DI

Communication

DI

Communication

* No. of outputs depends on specifications and models.



Isolated

* Outputs 3 to 7 are isolated.

------ Non-isolated