2) How to start self-tuning

* Self-tuning is a function to determine the PID constant when starting operation of the controller and

when changing the target value.

After determining the PID constant, self-tuning is not executed in the next start of operation, unless

the target value is changed.

* Self-tuning is executed when so set in the tuning type setting in SET 04 (control setting mode).
Auto-tuning is set at factory shipment.


For constant value run mode screen:

PV value (present value)

SV value (target value)

Hold MODE key pressed for 2 seconds.

Input 1 setting screen

Each set screen

Each setting mode

Press the ▲ key three times. Press it, however, twice for TTM-204.

Press MODE key 12 times.

S04-12 Tuning type setting screen

Control setting mode

* Tuning types are set in this screen.
* The number displayed in the screen matches with that listed in the tuning type

setting table.

* Use the ▲/▼ key for the setting.
* “1: primary auto-tuning” is set at factory shipment.
Changing the setting to “2: primary self-tuning” results in self-tuning.

Tuning type setting table

No.

Type

1

Primary auto-tuning

2

Primary self-tuning

3

Secondary auto-tuning

4

Secondary self-tuning

5

Primary/secondary auto-tuning

* Holding the MODE key pressed for 2 seconds moves each setting screen to the run mode screen.
* In about 2 minutes, each setting screen (or any setting screen) automatically moves back to the run mode

screen.

Hold

MO

DE

ke

y

pre

ss

ed

for

2

sec

onds

.

For program run mode screen:

PV value (present value)

SV value (PRoG)

Hold MODE key pressed for 2 seconds.

Setting mode is the same as that for Hereinafter,
to the input 1 setting screen similarly to that for
the constant value run mode