TOHO ELECTRONICS TTM200 User Manual

Page 236

Advertising
background image

48-7009-E

7-5

(3) Auxiliary output section

1)

No. of output points (see the table below)
2 points (TTM-204) Common shared
4 points (TTM-207)
For TTM-207, outputs 3 and 4 are for common shared and outputs 5 and 7 are for common independent. When
DI 3 exists, 4 points for 207.
5 points (TTM-205, 207 and 209)
For TTM-205 and 209, outputs 3 and 4 are for common shared and outputs 5 to 7 are for common independent.

2)

Output type (fixed per model designation)
① Relay contact output

a)

Contact type

1a contact

b)

Contact capacity

250 VAC, 1A (resistance loads)

c)

Min. loads

5 VDC, 100 mA

d)

Mechanical life

5 million counts or more

e)

Electric life

100 thousand counts or more
(More than 80 thousand counts at the UL approval)

f)

Isolation

Isolated from power circuit and CPU circuit

② Open collector output

a)

Output type

Open collector

b)

Output rating

24 VDC, 100 mA

c)

Leak current

0.3 mA or smaller (at output tuned off)

d)

Residual voltage

3 V or smaller (at output tuned on)

e)

Isolation

Isolated from power circuit and CPU circuit

3)

Connection method
Terminal block

Assignment of output functions

Type of output

Control output

Auxiliary output

Output 1

Output 2

Output 3

Output 4

Output 5

Output 6

Output 7

Primary output (heating)

Secondary output (cooling)

Transmission

Event

End output

: Output assignment possible
: Output assignment not possible
Assured accuracy for the transmission output is -10 % to +10 % of the output range.

(4) CT input section

1)

No. of input points

2 points

2)

Measurement current range

0 - 50.0 A

3)

Setting current range

0.0 - 30.0 A (at-ON current/at-OFF current)

4)

Setting resolution

0.1 A

5)

Setting accuracy

±5 % of full span (1.0 A or less to be out of accuracy)

6)

Disconnection detection

300 ms or longer for ON time of control output

7)

Adhesion detection

300 ms or longer for OFF time of control output

8)

Isolation

Isolated from power circuit and non-isolated from CPU circuit

9)

Connection method

Terminal block


(5) Event input section

1)

No. of input points

2 points (TTM-204 DI 1 and 2: Common independent)

3 points (TTM-207 DI 1, 2 and 3: Common independent)

4 points (TTM-205 and 209 DI 1 and 2: Common independent, and DI 3
and 4: Common shared)

2)

Input specification

No-voltage contact input

3)

Input polarity

Active switchover possible for each input

Close active/open active

4)

Function

See the operation specifications.

5)

At-ON current

Max. 10 mADC

6)

At-OFF voltage

Max. 6 VDC

7)

Min. input time

200 ms

8)

Allowable resistance value between terminals At ON, max. 333

and at OFF, min. 500 k

9)

Isolation

Isolated from power circuit and CPU circuit

10) Connection method

Terminal block

Advertising