6-32

■ Primary control sensitivity setting

SEt04

CNt

Setting content

Initial value

34

C1

Thermocouple/resistance temperature detector input
0.0 to 999.9 (

C)

0 to 999 (

C)

1

Voltage/current input
0 to 9999 (digit)

10

Set the primary control sensitivity.
Sensitivity (hysteresis) of ON/OFF operation is set. For heating control, the sensitivity is set below SV.

■ Primary control off-point position

SEt04

CNt

Setting content

Initial value

35

CP1

Thermocouple/resistance temperature detector input
-999.9 to 999.9 (

C)

-999 to 999 (

C)

0

Voltage/current input
-9999 to 9999 (digit)

Set the primary control off-point position.
Moving the off-point of the primary control sensitivity results in a move of entire range of the sensitivity.


<Reverse operation>

Off-point CP1 = 0

C1

ON

OFF

PV

Low

SV

High

Off-point CP1 = positive value

C1

CP1

ON

OFF

A point

PV

Low

SV

High

Off-point CP1 = negative value

C1

CP1

ON

OFF

B point

PV

Low

SV

High

C1: Sensitivity setting

C1: Sensitivity setting
CP1: Off-point position
A point: SV + CP1

C1: Sensitivity setting
CP1: Off-point position
B point: SV - CP1