4-24


Continued from the previous page

S04-9 Type B mode setting screen

* The type of the PID Type B mode is set in this screen.
* The number displayed in the screen coincident with that listed in the Type B mode setting table.
* Use the ▲/▼ key for the setting.
* The value is set at “1” at factory shipment.

Press MODE key.

S04-10 Forward/reverse operation setting screen

* Forward/reverse operation is set in this screen.
* The number displayed in the screen coincident with that listed in the forward/reverse operation

setting table.

* Use the ▲/▼ key for the setting.
* The value is set at “0” at factory shipment.

Press MODE key
three times.

S04-11 Tuning type setting screen

* The tuning types are set in this screen.
* The number displayed in the screen coincident with that listed in the tuning type setting table.
* Use the ▲/▼ key for the setting.
* The value is set at “1” at factory shipment.
* If the function is not specified for the equipment, corresponding screen is not displayed.








* Holding the MODE key pressed for 2 seconds moves each setting screen to the operating mode screen.
* In about 2 minutes, each setting screen (or any setting screen) automatically moves back to the operating mode screen.

Type B mode setting table

No.

Overshoot

0

Overshoot suppression - Moderate

1

Overshoot suppression - Intermediate

2

Overshoot suppression - Intense

Forward/reverse operation setting table

No.

Operation type

0

Forward operation

1

Reverse operation

Tuning type setting table

No.

Type

1

Primary auto-tuning

2

Primary self-tuning

3

Secondary auto-tuning

4

Secondary self-tuning

5

Primary/secondary auto-tuning