5.4.8 Position proportional control

■ What the position proportional control is

• In the position proportional control, the temperature of the subject is controlled through adjusting the

flow rate, which depends on the valve opening ratio. The valve opening ratio is controlled by open
or close signal that is output for the valve, where an operating amount is calculated by the PID
control, taking into account the valve motor stroke time. The position proportional control can
control a subject without feedback resistance.

• The valve motor stroke time is defined as time required for a valve from full close to full open.

Sensor

Open signal

Close signal

Controller

Subject of control

Warm water

Discharge of warm water

Valve

Warm

water

• Valve motor drive dead band
The controller for the position proportional control operates output of open or close signal such that

the operating amount of the controller is coincident with the valve opening ratio. To save service
life of the valve, frequent switchover operation for opening and closing the valve must be avoided as
much as possible.

Hence, a dead band is provided on the output switchover points for open and close signals, so that

outputs of both the open and close signals are halted in this band range in order to reduce the
frequency of open and close switchover operations.

Dead band

Opening ratio

MV

Open signal

Close signal

• Post-AT initial opening ratio
The operating amount can be set for suppressing undershoot that is possibly generated right after the

termination of AT.

Example: Response in post-AT

温度

初期開度=100%

初期開度=0%

AT中

通常制御

Temperature