Magnified drawing – TOHO ELECTRONICS TTM200 User Manual

Page 231

Advertising
background image

48-7009-E

6-83

Zone Threshold Switching Sensitivity Range Setting

SEt23

ZbNK

Setting Contents

Initial

Value

4

ASC

Zone Threshold Switching Sensitivity Range Setting 3

2

During Temperature Input

0~999(0.0~999.9)

(℃)

During Analog Input

0~9999

digit)

Sets the sensitivity setting for the threshold of

the bank auto-switching.

At bAF=0(OFF) and bAS=*0 or *1, there will

be nol indication when the SET02 LR=0.

When SET04 bANKH=0, the setting becomes
invalid.
There will be no indications either.

※4

Zone Threshold Switching Sensitivity Range Setting (ASC)

Sets the Sensitivity Range to each intermediate points to which the bank auto-switching is done.

Setting Range: During the Temperature Input 0~999(0.0~999.9)

(℃)

During the Analog Input 0~9999

digits)

NOTE: With Threshold (PM 1 to PM 7), it will be common value.

NOTE: It will be ±(ASC/2) with (PM1 to PM7) as the center.

As for the behavior, please refer to the “Zone Threshold Switching Sensitivity Range Setting

Behavior Diagram” below.

Zone Threshold Switching Sensitivity Range Setting Behavior Diagram
With each PM*Value as the center, the value set by ASC shall be the sensitivity range.

Auto-Switching

Source

BANK0

BANK1

BANK2

BANK3

BANK4

BANK5

BANK6

BANK7

PM1

PM2

PM3

PM4

PM5

PM6

PM7

SLH

SLL

PM*

(*=1~7)

Magnified

Drawing

ASC

When

"increasing"

Auto-Switching

Source

When

"decreasing"

Outset of

BANK

switching

Outset of

BANK

switching

Auto-Switching

Source

NOTE: This setting is effective only when the Bank Automatic Switching Source Setting (bAS) is selected

either Remote SV or PV.

Conditions when ASC can be set>

When (bAS = 2)
When SET02 (LR = 1, 2) at (bAS = 0)

Conditions when ASC cannot be set>

When (bAS = 1)
(bAS = 0) but when SET02 (LR = 0).