■ Where the equipment is used as a simplified programmable controller (manual start and event * start)

Setting example where temperature is raised to 100 °C in 1 minute, maintained at 100 °C for 1 minute,
and then lowered to 0 °C in 1 minute

SEt03

KEY

Name

Setting content

Setting value

FU1

Function key 1 function setting

No setting of time for the key held
pressed/timer start/reset

04

SEt7/8
oUt3/4

Name

Setting content

Setting value

o3F

Target connection setting

Timer 1 output

5

o4F

Target connection setting

Timer 2 output

9

SEt14

tIME1

Name

Setting content

Setting value

tMF1

Function setting

Manual-start

2

oNt1

On delay timer

0 minute

00:00

oFt1

Off delay timer

1 minute

00:02

SEt15

tIME2

Name

Setting content

Setting value

tMF2

Function setting

Event 3 start

10

oNt2

On delay timer

2 minutes

00:02

oFt2

Off delay timer

1 minute

00:01

SEt20

bNK

Name

Setting content

Setting value

bnk01

Control setting

SV

bnk02

Ramp time setting

RMP

For the following setting, enter the inputs during the switchover in bANK (bank switching) in SET 4.
* Set bANK to “0.”

SEt04

CNt

Name

Setting content

Setting value

SV

Control setting

0

C

0

RMP

Ramp time setting

Setting turned off

0.0

* Set bANK to “1.”

SEt04

CNt

Name

Setting content

Setting value

SV

Control setting

100

C

100

RMP

Ramp time setting

To be raised by 100 °C in 1 minute

100.0

* Set bANK to “2.”

SEt04

CNt

Name

Setting content

Setting value

SV

Control setting

0

C

100

RMP

Ramp time setting

To be raised by 100 °C in 1 minute

100.0


* The bank cannot be switched over unless DI is set after the bank setting is complete.

SEt13

dI

Name

Setting content

Setting value

dIF

Function setting

Both DI 1 and DI 2 to be switched over

0011

Wire the equipment upon completion of setting.