TOHO ELECTRONICS TTM200 User Manual

Page 165

Advertising
background image

48-7009-E

6-17

■ Primary control operating amount

SEt04

CNt

Setting content

Initial value

11

MV1

MLL 1 to MLH 1 (%)

0.0

The screen is for displaying the operating amount for the primary control.
The operating amount cannot be set for the normal control.
The operating amount can be set only when the control mode is set to manual.

■ Primary control output gain setting

SEt04

CNt

Setting content

Initial value

12

MV1G

0.0 to 1000.0 (%)

100.0

The operating amount (MV 1) for the primary control is multiplied by a compensation value.
[Operating amount for the primary control] = [Operating amount for the primary control before compensation] × [Primary
control output gain setting]

Note A change of the output gain setting may result in no provision of best suited PID parameter in AT.

Note Each limiter is output with a high priority, when the following is set: the primary control operating amount limiter upper limit

setting or primary control operating amount limiter lower limit setting.

Change of the output amount when the output gain setting is set to 70.0 %


100.0%

70.0%

50.0%

35.0%

Output operating
amount calculated

Operating amount

Output operating amount
that is actually output

SV temperature reached

Measurement temperature

Setting example:

When control characteristics in 100 VAC is desired to be maintained also in 120 VAC;
100 VAC and 100 W

120 VAC and 144 W, assuming that the heater resistance of 100

is identical for both 100 VAC and

120 VAC
100 W ÷ 144 W = 69.4 %
Thus, by setting the output gain setting to 69.4 %, control characteristics in 120 VAC can be expected to be analogous to those
in 100 VAC.

NOTE: In case the loop disconnection is used when the output gain setting is at 50.0%, make the working volume limiter the same as
that of output gain.