■ Secondary control proportional cycle

SEt04

CNt

Setting content

Initial value

41

t2

0.1 to 120.0 (seconds)

20.0

Set the secondary control proportional cycle.
Relay contact output, voltage output for SSR drive or open collector output has only the state of ON or OFF for output, and
thereby no proportional operation is offered.
Thus, to solve the issue, concept of time proportional operation is applied.
In the time proportional operation, ON/OFF is repeated in a proportional cycle (time cycle), where the ON state is maintained
for a particular time period and the OFF state for the rest of the period.

Example: When the proportional cycle is 20 seconds and the operating amount (MV) is 40 %, the ON/OFF period is as

follows.

ON: 8 seconds
OFF: 12 seconds


ON

OFF

Proportional cycle