TOHO ELECTRONICS TTM200 User Manual

Page 185

Advertising
background image

48-7009-E

6-37

■ Secondary control operating amount change limiter ascent setting

SEt04

CNt

Setting content

Initial value

44

oU2

0.0 to 549.9 (%)
Function turned off at 0.0 (%) setting

0.0

Set the secondary control operating amount change limiter ascent.

A limit is set to the ascent percentage of the operating amount change calculated.
An operating amount allowed with ascent for a second is set in the unit of percentage.

Calculated

operating amount

Limited operating

amount

100%

100%

0%

0%

Time

MLL 2 is set for the initial MV at power-on.

Note

(1) The setting is effective also during AT.
(2) When the setting is changed, re-AT is required due to different control result.
(3) The setting value of 100 % allows ascent of only 20 % in the input sampling (200 ms).

In order to have ascent of 100 % in the input sampling (200 ms), set the setting value to 500 %.

(1 s ÷ 200 ms) × 100 % = 500 %

Set the setting value to 0.0 % (OFF) when ascent of 110 % from 0 % in a second is desired for an analog input.

■ Secondary control operating amount change limiter descent setting

SEt04

CNt

Setting content

Initial value

45

od2

0.0 to 549.9 (%)
Function turned off at 0.0 (%) setting

0.0

Set the secondary control operating amount change limiter descent.

A limit is set to the descent percentage of the operating amount change calculated.
An operating amount allowed with descent for a second is set in the unit of percentage.

100%

100%

0%

0%

Calculated

operating amount

Limited operating

amount

Time

MLL 2 is set for the initial MV at power-on.

Note

(1) The setting is effective also during AT.
(2) When the setting is changed, re-AT is required due to different control result.
(3) The setting value of 100 % allows descent of only 20 % in the input sampling (200 ms).

In order to have descent of 100 % in the input sampling (200 ms), set the setting value to 500 %.

(1 s ÷ 200 ms) × 100 % = 500 %

Set the setting value to 0.0 % (OFF) when descent of 110 % from 0 % in a second is desired for an analog input.

Advertising