48-7009-E

6-2

6.1

Input 1 type setting

■ Input 1 type setting

SEt01

INP1

Setting content

Initial value

1

INP1

Press the MODE key for making a setting effective (including reverse feed).

0

0 to 20

See the input 1 type setting table.

Set the input type of the input 1.

The input 1 is for a multi-input for thermocouple, resistance temperature detector, voltage and current. Set according to the
input being used.


Input 1 type setting table

Setting

No.

Input type

Connection

Measurement/

setting range

Indicator

resolution

Accuracy

0

K thermocouple

TC

-200.0 to +1372.0

1

C / 0.1

C

Either larger ± (0.3 % + 1 digit) or ± 2°C
Note: ± 3°C for - 100.0 to 0.0°C and ± 4°C for
- 200.0 to - 100.0°C
No specification for 400°C or lower for B
thermocouple

1

J thermocouple

TC

-200.0 to +1200.0

1

C / 0.1

C

2

T thermocouple

TC

-200.0 to + 400.0

1

C / 0.1

C

3

E thermocouple

TC

-200.0 to +1000.0

1

C / 0.1

C

4

R thermocouple

TC

-50 to +1768

1

C

5

S thermocouple

TC

-50 to +1768

1

C

6

B thermocouple

TC

0 to +1800

1

C

7

N thermocouple

TC

-200.0 to +1300.0

1

C / 0.1

C

8

U thermocouple

TC

-200.0 to +400.0

1

C / 0.1

C

Either larger ± (0.3 % + 1 digit) or ± 4°C
± 6°C for lower than 0°C

9

L thermocouple

TC

-200.0 to +900.0

1

C / 0.1

C

10

WRe5-26 thermocouple

TC

0 to +2300

1

C

Either larger ± (0.6 % + 1 digit) or ± 4°C

11

PR40-20 thermocouple

TC

0 to +1880

1

C

± 9.4°C

1 digit

No specification on accuracy for lower than
800°C

12

PL II thermocouple

TC

0.0 to +1390.0

1

C / 0.1

C

Either larger ± (0.3 % + 1 digit) or ± 2°C

13

Pt100

RTD

-200.0 to +850.0

1

C / 0.1

C

Either larger ± (0.3 % + 1 digit) or ± 0.9°C

14

JPt100

RTD

-200.0 to +510.0

1

C / 0.1

C

15

0 - 10 mVDC

TC

-19999 to +29999
Display resolution to be
20000 or less
*1

Random
change of
decimal point
position
allowed

±0.5 % ±1 digit of full scale

16

0 - 1 VDC

I/V

±0.3 % ±1 digit of full scale

17

0 - 5 VDC

I/V

18

1 - 5 VDC

I/V

19

0 - 10 VDC

I/V

20

4 - 20 mADC

I/V

*1 The display range of analog input is min. - 19999 digits and max. +29999 digits. The range, however, can be narrowed by

setting the scaling upper limit (FSH 1) and lower limit (FSL 1) settings. See below for the narrowed display range.
<Where input is 0 - 10 mV/0 - 1 V/0 - 5 V/0 - 10V>

• Display of the lower limit side: Up to - 2 % of the full scale
• Display of the upper limit side: Up to + 12 % of the full scale

<Where input is 1 - 5 V/4 - 20 mA>

• Display of the lower limit side: Up to - 12 % of the full scale
• Display of the upper limit side: Up to + 12 % of the full scale


Full scale is defined as the range from FSL 1 to FSH 1.

The display range for temperature input (setting Nos. of 0 to 12 in the table above) is fixed.