■ Regarding repetitive run

A repetitive run of a designated step can be executed during a program run. Any step (as a whole or
part) of program steps set in SET 22 can be repeated.

The diagram below shows an example of using this function where the steps 2 and 3 of total 4 steps are
repeated 3 times.


STEP1

STEP2

STEP3

STEP2

STEP3

STEP2

STEP3

STEP4

A program

run begins.

Repetitive start step: STEP 2
Repetitive end step: STEP 3
Repeat count: 3 times

A program

run ends.


The following parameters of SET 22 are used for the repetition setting in program setting mode.

SEt22

PROG

Setting content

Initial

value

5

StRSt

Repetitive start step setting

1

Setting value range: 1 to repetitive end step setting [ENdSt]

6

ENdSt

Repetitive end step setting

StEPN

Repetitive start step setting [StRSt StRSt] up to the
number-of-use-step setting or StEPN
* If StEPN is set, the value set for the number-of-use-step setting

is a setting for “repetitive end step setting.”

7

RUNP

Execution count setting

1

Setting value range: RUNP

0 to 9999

RUNP

0: Unlimited count

In the above example, the setting values are: StRSt

2, ENdSt

3 and RUNP

3.


Use the parameters listed below for the program step data setting in program setting mode.

(Setting regarding the program step data)

SEt22

PROG

Setting content

Initial

value

1

StEPN

Number-of-use-step setting

8

Setting value range: n = 1 to 8

2

St*bK

Step* designated bank setting

0

Setting value range: St*BK = 0 to 7

* = 1 to 8

3

SV*

Step SV* value

0

Setting range value: SV* = SLL to SLH

* 1 to 8

* If SLL or SLH are set in a bank, the value of SLL or SLH is set

for each bank.

4

tIM*

Step* time

00:00

Setting value range: TIM* = 00:00 to 99:59

* = 1 to 8

* With 00:00, a run unlimitedly continues.