7 di setting, Di setting -59, Di function setting – TOHO ELECTRONICS TTM200 User Manual

Page 207

Advertising
background image

48-7009-E

6-59

6.7 DI setting

■ DI function setting

SEt13

dI

Setting content

Initial value

1

dIF

Press the MODE key for making a setting effective (including reverse feed).

0000

****
||||
|||+-- DI 1 setting (settable when an option existent)
||+--- DI 2 setting (settable when an option existent)
|+---- DI 3 setting (settable when an option existent)
+----- DI 4 setting (settable when an option existent)

Active

0

None

None

1

Bank switchover

Bank switchover

2

When Constant operation
Mode

MD


When Program Mode

Start

When Constant operation
Mode

READY


When Program Mode

stop

3

MD

MANUAL

4

Reverse operation

Forward operation

5

AT stop

AT start

6

Timer stop

Timer start

7

Constant Operation Mode

Program Mode

3

8

Step Forward

3

(during program mode)

9

Pause

3

(during program mode)

A

nerlock

3

Set the DI function.

0: No DI function
1: Bank switchover is executed.

Bank selection table per DI 1 state

DI1

DI3

DI2

DI1

0

Bank 0

0

0

0

Bank 0

1

Bank 1

0

0

1

Bank 1

0

1

0

Bank 2

DI2

DI1

0

1

1

Bank 3

0

0

Bank 0

1

0

0

Bank 4

0

1

Bank 1

1

0

1

Bank 5

1

0

Bank 2

1

1

0

Bank 6

0: Inactive
1: Active

1

1

Bank 3

1

1

1

Bank 7


The parameters change right after switchover when the bank is changed per DI.

2: <During Constant Operation Mode> Switching of Control Mode and STOP.

<During the Program Mode> Switching of In-Operation and Operation Stop.

3: Switching of AUTO & MANUAL is done

4: Switching of Output Movement (forward / reverse movement) is done.

5: The Star & Stop of Auto-Tuning of PID Control is done.

Maintain the DI to active condition until the auto-tuning is completed.

In case the operation is suspended half-way, the auto-tuning will stop.