5.6 Explanation of the bank automatic switching function

■ Regarding the bank automatic switching function

The bank function can be automatically switched for each temperature. Setting control parameters for
each temperature beforehand enables realization of optimization and an accurate control. As
parameters unrelated to control can also be set similarly to the case of the normal bank function,
application for each temperature is possible for such functions as the timer and event functions.

Note Precaution when using this function together with the program run function

When using this function together with “program run,” the setting is ineffective even when the
bank designation is set using SET 22 “St*bK step* designated bank setting.” All banks are used
with priority when using the bank automatic switching function [SET 23 BAF

1]. Note that a

bank cannot be divided into parts for assigning one of them to, for example, a program run.



(Behavior diagram for explaining the bank automatic switching run)

SV

SLL

Threshold B: PM1 = 140, PM2 = PM3 =
PM4 = PM5 = PM6 = PM7 = SLH

8BANK (All Threshold * Setting <PM1 to PM7>)

Z

o

n

e

t

h

re

s

h

o

ld

s

e

tt

in

g

Refer

The designated bank is automatically switched

according to the bank automatic switching source.

SV
value

PM7≦
<SLH

SLL≦
<PM1

PM1≦
<PM2

PM2≦
<PM3

PM3≦
<PM4

PM4≦
<PM5

PM5≦
<PM6

PM6≦
<PM7

SET 20
setting value

M

a

x

.

1

6

p

a

ra

m

e

te

rs

Max. 8BANK (Zone threshold = 7)

Bank 0

Bank 1

Bank 2

Bank 3

Bank 4

Bank 5

Bank 6

Bank 7

RMP

RMP

10

RMP

10

RMP

10

RMP

10

RMP

5

RMP

5

RMP

10

P1

3.0

P1

4.0

P1

4.0

P1

4.0

P1

4.0

P1

2.0

P1

2.0

P1

4.0

I

0

I

20

I

20

I

20

I

20

I

10

I

10

I

20

D

0

D

5

D

5

D

5

D

5

D

2

D

2

D

5

PM* setting

value

Bank

auto-switching

source

Bank

No.

SLH

200

C

Bank 7

PM7

160

C

⑤150

C

Bank 7

PM6

140

C

Bank 6

PM5

120

C

Bank 5

PM4

90

C

④100

C

Bank 4

PM3

60

C

③70

C

Bank 3

PM2

40

C

Bank 2

PM1

20

C

②35

C

Bank 1

SLL

0

C

①10

C

Bank 0

PM1

PM2

PM3

PM4

PM5

PM6

PM7

Bank 6

Bank 5

Bank 4

Bank 3

Bank 2

Bank 1

Bank 0

Bank 7

SLH

Eight banks at most (threshold

7) can be used; the diagram is an example of all banks used. The

bank can automatically be switched for each temperature. The zone threshold* setting < PM 1 to PM
7 > is set in the SV value setting range from SLL to SLH.

The threshold required for automatic switching is set in SET 23 “bank automatic switching function
setting mode.”

For this function, SET 20 “bank function” must be set beforehand.