5 control setting mode (set 04) (1/4), Control setting mode (set 04) (1/4) -16 – TOHO ELECTRONICS TTM200 User Manual

Page 247

Advertising
background image

48-7009-E

7-16

7.5.5 Control setting mode (SET 04) (1/4)

Setting data

Character

Setting (monitor) value

Initial value

Unit

Setting

value

Blind

Bank switchover

bANK

0: Bank 0

0

None

1: Bank 1

2: Bank 2

3: Bank 3

4: Bank 4

5: Bank 5

6: Bank 6

7: Bank 7

Bank upper limit
setting

bANKH

0 to 7

7

None

Control setting

SV

SLL to SLH

0

C

SV limiter upper limit

SLH

Temperature:

(SLL + 5.0) to SV setting range
upper limit

(SLL + 5) to SV setting range
upper limit

Analog:

(SLL + 50) to SV setting range
upper limit

1200

C


Digit

SV limiter lower limit

SLL

Temperature:

SV setting range lower limit to
(SLH - 5.0)

SV setting range lower limit to
(SLH - 5)

Analog:

SV setting range lower limit to
(SLH - 50)

0

C


Digit

Control mode

Md

RDY: Control stop
RUN: Control start
MAN: Manual
TIME 1: Timer 1 operation
TIME 2: Timer 2 operation
TIME 3: Timer 3 operation

RUN

None

Control type

CNt

0: Primary nonexistent
Secondary nonexistent
1: Primary PID control
Secondary nonexistent
2: Primary ON/OFF control
Secondary nonexistent
3: Primary PID control
Secondary PID control
4: Primary PID control
Secondary ON/OFF control
5: Primary ON/OFF control
Secondary ON/OFF control
6: Primary position proportional
Secondary position

proportional

1

None