TOHO ELECTRONICS TTM200 User Manual

Page 209

Advertising
background image

48-7009-E

6-61

Setting example:

When “AT start” is assigned to DI 1 (close active)

Set dIF to 0005 and dIP to 0000.

When DI is inactive

200

200

200

At

Switch OFF

DI1

Lighting

When DI is active

Switch ON



Usable DIs for each product model
DIs indicated in the table are usable when DI types are optionally designated.

TTM-204

TTM-205
TTM-209

TTM-207

DI1

DI2

DI3

DI4


■ DI polarity setting

SEt13

dI

Setting content

Initial value

2

dIP

****
||||
|||+-- DI 1 setting (settable when an option existent)
||+--- DI 2 setting (settable when an option existent)
|+---- DI 3 setting (settable when an option existent)
+----- DI 4 setting (settable when an option existent)

0000

0

Close active

1

Open active


“Close active” or “open active” is set for “DI function setting” described above.

Close active: DI is active when short (max. 333

) is established between DI terminals.

Open active: DI is active when release (min. 500 k

) is established between DI terminals.