TOHO ELECTRONICS TTM200 User Manual

Page 151

Advertising
background image

48-7009-E

6-3

Input 1 connection table

Model

TTM-200 Series

Model No.

204

205
209

207

Connection

Wiring

Terminal No.

Terminal No.

Terminal No.

TC

12

11

24
23

18
17

RTD

A
B

b

12

11

10

24
23
22

18
17
16

I/V

10

11

22
23

16
17

Note Switchover of the input types may result in change of each setting value due to limits being applied, such as SLH, SLL,

tRH and tRL.


■ Display scaling upper limit/lower limit setting

SEt01

INP1

Setting content

Initial value

2

FSH1

Voltage/current input only
FSL 1 to 29999 (digit)

10000

3

FSL1

Voltage/current input only
-19999 to FSH 1 (digit)

-10000

Display scaling upper limit/lower limit are set for the input 1.

This setting is possible only when the input 1 is set for voltage/current input.

Setting example: Where the input type is the 4 - 20 mA setting and the display range is 0.0 digit for 4 mA and 100.0 digits

for 20 mA.
Set as INP 1: 20, FSH 1: 100.0, FSL 1: 0.0 and dP 1: 0.0.
* For this setting, the display range is - 12.0 to 112.0.
For -12.0 or smaller, the display is “underscale display.”
For 112.0 or larger, the display is “overscale display.”

PV

Input 1

4mA

20mA

100.0%(FSH1)

0.0%(FSL1)

Note

(1) Display resolution is 20,000 or less.

Take care it when the range from FSL 1 to FSH 1 is set larger than 20,000.

Setting example: Fluctuation or missing value of PV may be caused when the input 1 is set to the input type of 4 - 20 mA,
FSL 1 to -19999 digits and FSH 1 to 29999 digits.

(2) Take care that setting values for FSH 1 and FSL 1 can be the same.