TOHO ELECTRONICS TTM200 User Manual

Page 163

Advertising
background image

48-7009-E

6-15

■ Control mode

SEt04

CNt

Setting content

Initial value

6

Md

RUN

Control start

RUN

MAN

Manual

RdY

Control stop

tIME1

Timer 1 operation

tIME2

Timer 2 operation

tIME3

Timer 3 operation

Set the control mode.
Control stop (RdY): Primary/secondary operating amount limiter lower limit is output.
Control start (RUN): Normal control is executed.
Manual (MAN): Operating amount set in the primary/secondary operating amount is output.
Timer interlocking control (tIME 1 to 3): A control where the normal control and timer operation are interlocked is executed.

For start (RUN)/stop (RdY)/manual (MAN) of control, see section “5.4.3 Mode/manual function” on page 5-28.

For timer interlocking control (tIME 1 to 3), see section “5.4.5 Timer function” on pages 5-32 to 37.

■ Control type setting

SEt04

CNt

Setting content

Initial value

7

CNt

0

Primary --- None

Secondary --- None

1

1

Primary --- PID control

Secondary --- None

2

Primary --- ONOFF control

Secondary --- None

3

Primary --- PID control

Secondary --- PID control

4

Primary --- PID control

Secondary --- ONOFF control

5

Primary --- ONOFF control

Secondary --- ONOFF control

6

Primary --- position proportional

Secondary --- position proportional

Set the control type (method).
Control types of primary and secondary control outputs that are set on this equipment can be assigned to the methods of 0 to 6.
For the content of the assignment, see the setting content listed above.

Note

(1) In case that the control type is set to 3 (primary/secondary PID control) and the tuning type to 3, 4 or 5, take care that the tuning

type changes to 1 (primary tuning) in conjunction with the change of the control type.

(2) Take care that the position proportional control (CNt: 6) is selectable even when the primary/secondary control output is not set

for the target connection setting.


■ PID control type/type B mode

SEt04

CNt

Setting content

Initial value

8

tYP

0

type A (normal PID control)

1

1

type B (overshoot suppression function)

2

type C (disturbance suppression function)

9

bMd

0

Overshoot suppression --- moderate

1

1

Overshoot suppression --- intermediate

2

Overshoot suppression --- intense

Set the PID control type.
For the use of the equipment in setting of the control type to be the PID control, a selection can be made among three control types of
0 (type A) to 2 (type C), whichever is best suited for the application.

Note The type B mode can be set when the PID control type is set to 1 (type B). In the type B mode, a result from integration (I) or

differentiation (d) of the auto-tuning is multiplied by a coefficient. The intermediate type is same value as it is. The type C
(disturbance suppression function) cannot be set when the self-tuning is set in the tuning type setting.

For control characteristics of each control type, see section “5.4.1 Auto-tuning (AT) function” on pages 5-23 to 25.