■ Primary control soft-start output setting

SEt04

CNt

Setting content

Initial value

26

SFM

ML 1 to MH 1 (%)

100.0

Set the primary control soft-start output setting.

A limit is set in a particular time period (or the primary control soft-start time) on the operating amount calculated.

■ Primary control soft-start time setting

SEt04

CNt

Setting content

Initial value

27

SFt

00:00 to 499:59 (minute seconds)

000:00


Soft-starting

PID control

Primary control soft-

start output setting

Power-on

Operating amount

(%)

Time elapsed

Note

(1) The SOFT START operates both when the power is switched ON and when the Control Mode is

switched from "READY to RUN".

The switching of the Control Mode can be done with setting such as (SEt04 Md)(SEt03 FU*) and

SEt13 DIF)

(2) Soft-start is effective only during equipment operation. Note that the time elapses even after the mode changes to

control stop, manual or AT.

(3) The set time can be changed during soft-start, where the set time is the time from power-on.

Example 1) When the set time is changed from 6 minutes to 4 minutes in 5 minutes after power-on, soft-start

immediately stops.

Example 2) When the set time is changed from 6 minutes to 8 minutes in 5 minutes after power-on, soft-start will stop

in 3 minutes.