5-77

■ Regarding the “bank function” priority

If multiple settings are set for the bank switching designation, bank switching is applied from of a
function with a higher priority.


The following applies (“1” is of the highest priority).

1. “Bank automatic switching function”

SET 23 [PM*] zone threshold* setting (“*”: Zone No.)


2. “Program run”

SET 22 [St*bK] step* designated bank setting (“*”: Step No.)


3. “Switching with DI”

SET 13 DIF

**** (when “*”

1)


4. “Switching with the function key”

SET 3 FU*

7 (“*”: Key No.)


5. “Setting value of SET 4 bBNK”

bBNK

* (“*”: Bank value)

Note Note that, if multiple designations of 1 to 5 above are set, the designation with a lower priority is

disregarded.