10 timer 1 to 3 setting modes (set 14, 15 and 16), Timer 1 to 3 setting modes (set 14, 15 and 16) -27 – TOHO ELECTRONICS TTM200 User Manual

Page 258

Advertising
background image

48-7009-E

7-27

7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)

Setting data

Character

Setting (monitor) value

Initial value

Unit

Setting

value

Blind

Timer function

tMF1
tMF2
tMF3

1: Auto-start
2: Manual start
3: SV start
4: DI 1 start
5: DI 2 start
6: DI 3 start
7: DI 4 start
8: Event 1 start
9: Event 2 start
10: Event 3 start
11: Event 4 start
12: Event 5 start
13: Event 6 start
14: Event 7 start
15: Step start *1
16: Soak start *1

1

None

Unit

H/M1
H/M2
H/M3

1: Hour/minute
2: Minute/second

1

Hour/

minute/
second

Start SV permissible
range

tSV1
tSV2
tSV3

Temperature: 0.0 to 999.9

0 to 999

Analog: 0 to 9999

C

Digit

ON delay timer

oNT1
oNT2
oNT3

0:00 to 99:59

0:00

Hour/

minute/
second

OFF delay timer

oFt1
oFt2
oFt3

0:00 to 99:59

0:00

Hour/

minute/
second

Repeat count

RUN1
RUN2
RUN3

0 - 99 (infinite with 0)

1

Count

Remaining time
monitor

tIA1
tIA2
tIA3

0:00 - 99:59
Start/stop with the ▲/▼ key

0:00

Hour/

minute/
second

*1: Selectable only on Ver3.xx or later.