48-7009-E

6-80

6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING

Bank Automatic Switching Function Selection

SEt23

ZbNK

Setting Contents

Initial

Value

1

bAF

Bank Automatic Switching Function Selection 3

0

0

Bank Auto-Switching Operation OFF

1

Bank Auto-Switching Operation ON

In case the “Bank Auto-Switching Operation

ON” is set;

The Bank Switching Setting with the FUNC

Key will be invalid.

The Bank Switching Setting by DI will be

invalid.

▲▼

key operation will not be possible either.

When SET04 bANKH=0, the setting will be

invalid.

There will be no indication either.

※1

Bank Automatic Switching Function Selection (bAF)

This is to set the Bank Automatic Switching ON/OFF. When ON, the bank will be switched

automatically with the selected input by the Bank Automatic Switching Source Setting (bAS).

Setting Range:When 0: Bank Automatic Switching Operation OFF

When 1: Bank Automatic Switching Operation ON

Behavior Diagram when Bank Automatic Switching is ON

BANK1

RMP

10

P1

4.0

20

5

BANK2

RMP

10

BANK3

RMP

10

BANK4

RMP

10

BANK5

RMP

5

BANK6

RMP

5

BANK7

RMP

10

BANK0

RMP

P1

3.0

MA
X

.16
param

et

er

0

0

SV

P1

2.0

10

2

P1

4.0

20

5

P1

4.0

20

5

P1

4.0

20

5

P1

4.0

20

5

P1

2.0

10

2

SET20
setting

Refer

BANK0

BANK1

BANK2

BANK3

BANK4

BANK5

BANK6

BANK7

PM1

PM2

PM3

PM4

PM5

PM6

PM7

SLH

SLL

SLL≦

<PM1

SV

value

PM1≦
<PM2

PM2≦
<PM3

PM3≦
<PM4

PM4≦
<PM5

PM5≦
<PM6

PM6≦
<PM7

PM7≦
<SLH

Bank Automatic Switching.

Switch the bank in accordance with

the source(SV)..

MAX. 8BANK

① 10℃

PM*

setting

PM1

PM2

PM3

PM4

PM5

PM6

PM7

SLL

SLH

20℃

0℃

40℃

60℃

90℃

120℃

140℃

160℃

200℃

② 35℃

Bank 0

Bank 1

Bank 2

Bank 3

Bank 4

Bank 5

Bank 6

Bank 7

③ 70℃

④ 100℃

⑤ 150℃

Auto-Switching

sorce

Bank No.

8BANK(All Threshold*Setting <PM1 to PM7)>)

Bank 7

Zone

Threshold

Setting

NOTE: When the Bank Automatic Switching Function is (SET23 bAF = 1), please note the following points in

case the parameters “SV, SLL, SLH” is set at SET 20 (Bank);

The value of the “SV, SLL, SLH” set at the Bank will be invalid.

The Bank registration of “SV, SLL, SLH” will be erased and will go back to the default value.
If (SET 23 bAF = 0) again, the bank registration of “SV, SLL, SLH” are erased, so there is a need to reset.