5-38

5.4.6 Loop abnormality function

■ What the loop abnormality is

The function is to detect an abnormality in the control loop.

When a value falls in the judgment domain with respect to the conditions of the control loop

anomaly MV threshold(MS*) and control loop anomaly PV threshold(tS*), the control loop anomaly
PV change threshold is judged at each “LoP*” time.

A loop abnormality is determined if each change threshold is judged to be equal to or below “PS*.”

When [PS* = 0] is true, only time judgment is executed using LOP*.

When the time satisfying threshold of TS* or MS* exceeds LOP*, the loop abnormality is

determined as detected.

(The symbol “*” takes the following values: “1” for the primary control and “2” for the secondary

control.)

The loop abnormality function is usable when one of OUT 1 to OUT 7 is selected for the event
loop abnormality existent.
About primary control loop abnormality-related setting ............................. P6-24~27
About secondary control loop abnormality-related setting .......................... P6-37~40
About event function 4 loop abnormality(E1~7F4) setting ......................... P6-44

Monitoring

time

(LoP*)

ON

OFF

SV

PV

MLL*

MLH*

MV*

Monitoring

time

(LoP*)

Monitoring

time

(LoP*)

Loop

abnormality

Judgment

domain

Non-

judgment

domain

Judgment

domain

Non-

judgment

domain

Control loop

anomaly PV

threshold

(TS*)

Control loop

anomaly MV

threshold

(MS*)

Advertising