TOHO ELECTRONICS TTM200 User Manual

Page 109

Advertising
background image

48-7009-E

5-39

< How to set >

Power-on

About 4 seconds (automatic)

Operating mode

MODE key: 2 seconds

Input 1 setting mode

SET 01 screen

△/▽ key

Control setting mode

SET 04 screen

MODE key

Primary control loop

abnormality time setting

LoP 1

Set the primary control abnormality
time setting, using the △/▽ key.

Secondary control loop

abnormality time setting

LoP 2

Set the secondary control abnormality
time setting, using the △/▽ key.

Control setting mode

SET 04 screen

OUT 1 to 7 setting mode

SET 05 to 11 screens

Set the screen to OUT * output screen, which is used for
outputting the loop abnormality, using the △/▽ key.
(Select among OUT 1 to 7.)

Target connection setting

o * F

Set it to the event output “2”, using
the △/▽ key.

Event function 4 setting

E * F 4

Set it to “01” of the loop abnormality existent
and “11” of the loop abnormality existent +
hold existent, using the △/▽ key.

Setting complete

MODE key

MODE key

△/▽ key

MODE key

MODE key


How to cancel the loop abnormality hold
(1) Set the additional function setting of the event function 4 setting to “0: None.”
(2) Turn off the power when no abnormality is present, and then turn it back on.

Advertising