TOHO ELECTRONICS TTM200 User Manual

Page 135

Advertising
background image

48-7009-E

5-65

This section introduces the timer function. Timer behavior is determined by defining the following
parameters: timer function setting [tMF 1 to tMF 3], unit setting [H/M 1 to H/M 3], SV start allowable
range setting [tSV 1 to tSV 3], On delay timer [oNt 1 to oNt 3], Off delay timer [oFt 1 to oFt 3],
repetition count setting [RUN 1 to RUN 3], etc.

(Timer function setting)

SEt14

tIME1

to

SEt16

tIME3

Setting content

Initial

value

1

tMF1

to

tMF3

1 Auto start

1

2 Manual start

3 SV start

4 DI 1 start (settable when an option existent)

5 DI 2 start (settable when an option existent)

6 DI 3 start (settable when an option existent)

7 DI 4 start (settable when an option existent)

8 Event 1 start

9 Event 2 start

10 Event 3 start (settable when an option existent)

11 Event 4 start (settable when an option existent)

12 Event 5 start (settable when an option existent)

13 Event 6 start (settable when an option existent)

14 Event 7 start (settable when an option existent)

15 Step start

16 Soak start


(Unit setting)

Setting content

Initial

value

2

H/M1

to

H/M3

1 Hour/minute

1

2 Minute/second


If the SV start is set, set the temperature in

C or the digit width range which a timer starts.

(SV start permissible range setting)

Setting content

Initial

value

3

tSV1

to

tSV3

Thermocouple/resistance temperature detector input
0.0 to 999.9 (

C)

0 to 999 (

C)

0

Voltage/current input
0 to 9999 (digit)


• The allowable range is set in range of tSV with its center at the SV value as illustrated below.

SV value

tSV

• If tSV is set to 1.0

C, the timer becomes active when a temperature falls within the SV value

0.5

C.

Note If the ramp function is also used, tSV is attached to a target SV value.