TOHO ELECTRONICS TTM200 User Manual

Page 204

Advertising
background image

48-7009-E

6-56

■ Output 1 and 2 transmission scaling upper limit/lower limit setting

SEt05

oUt1

to

SEt06

oUt2

Setting content

Initial value

12

tRH1

to

tRH2

Thermocouple/resistance temperature detector input
tRL* to 2999.9 (

C)

tRL* to 2999 (

C)

1200

Voltage/current input
tRL* to 29999 (digit)

12000

13

tRL1

to

tRL2

Thermocouple/resistance temperature detector input
-1999.9 to tRH* (

C)

-1999 to tRH* (

C)

0

Voltage/current input
-19999 to tRH* (digit)

Set the transmission scaling upper limit/lower limit of the transmission output.
The output 1 or output 2 being set for analog output can be used as a transmission output.
For using the output 1 or 2 as a transmission output, set 17 (transmission output) for the target connection of the output 1 or 2.

This function is to scale the transmission output range with respect to the measurement/setting value.
The decimal point position is set in conjunction with the decimal point position setting (dP 1).

Note This function cannot be set when “3” or “4” (primary/secondary control operating amount) is set in the transmission output

function setting.


Example: When transmitted in the following setting

Output 1

Output 2

Output type

Current 4 - 20 mADC

Current 4 - 20 mADC

Output target connection setting

o1F=17

o2F=17

Transmission output function setting

tRN1=01

tRN2=11

Transmission scaling upper limit

tRH1=1200.0

tRH2=1200.0

Transmission scaling lower limit

tRL1=0.0

tRL2=0.0


0

20

0

1200

PV transmission (forward operation)
PV transmission (reverse operation)

Output current [mA]

PV [

C]

4