■ Ramp time setting

SEt04

CNt

Setting content

Initial value

57

RMP

Thermocouple/resistance temperature detector input
0.0 to 999.9 (

C/minute)

0.0

Voltage/current input
0 to 9999 (digit/minute)

0

Set the ramp time.
A change of SV per minute is set when SV is changed.
The ramp control starts from the present PV.

<Start condition>

(1) At power-on
(2) SV change when bank being switched over
(3) When RDY being switched over to RUN

SV

* Settable at bank setting

The setting value changes from the
temperature at start of the operation to SV,
using the operating amount set for RMP.

SV

RMP

1 minute

Time

At start


Note Event output during ramp

The SV during ramp is equivalent to the SV for deviation upper/lower limit, deviation upper limit, deviation lower limit and
deviation range.
Take care that SV is not a final target value.

Note In the case of ramp setting (RMP = 0), the ramp function does not work.